Camp Water Supply - Well Pump, Tank and Booster

✏️
Input Data
Enter your project data
Total number of people living in the camp
ShNQ 2.04.01-22 Annex 3 item 2: maximum day 100 / 120 / 160 L per person
Daily water per person on the maximum day
Water per person in the maximum hour
Annex 3 item 16: 12 L per meal (incl. dish washing)
Meals cooked in the camp kitchen
Time in which the main meal is served - gives the kitchen peak hour
Annex 3 item 8: 75 L/kg mechanised, 40 L/kg non-mechanised
Work clothes, bed linen, towels
Gives the laundry peak hour
Ground tank: the booster feeds the camp. Elevated tank: gravity is checked first, the booster covers only the difference
Elevated tank only
Added to the tank volume; the well pump refills it within the refill time
ShNQ 2.04.02-19 Table 7 (e.g. 10 L/s for small 1-2 storey buildings)
ShNQ 2.04.02-19 2.30: 3 h
Time to refill the fire reserve after a fire
Water level in the well when the pump is off
From the pumping test; dynamic level = static level + drawdown
Enter the real value (well log / pump installation). At least 3 m below the dynamic level, at least 2 m above the well bottom
For the setting depth check
Length of the rising main on the ground
Negative when the tank is lower than the well head
Delivery main to the camp entrance
Negative when the camp is lower than the tank
Required free head at the entrance = 10 m + 4 m per floor above the first
All draw-off points (washbasins, showers, WCs, sinks, washing machines). 0: estimated from the persons
Added to the daily demand (leaks, flushing)
The float valve inlet is at the top of the tank
Tank volume = daily demand × days (+ fire reserve)
Safe yield from the pumping test
The tank covers the rest of the day
Pressure needed at the tank inlet valve
PE100 SDR11 outside diameter
Suction pipe length
PE100 SDR11 outside diameter
PE100 SDR11 outside diameter
Own value instead of 10 + 4·(n − 1)
Yard network from the camp entrance to the farthest building
Fixed speed with pressure switch and diaphragm tank, or variable speed (VSD)
Plus one standby pump
Pressure switch difference
From the motor data (small motors 20-30, larger 10-15)
Hazen-Williams, KMK / SNiP plastic pipes or Darcy-Weisbach
140 for PE pipes
ShNQ 2.04.01-22 item 120: 30 % for domestic water networks
For the automatic pipe size (suction ≤ 1.2 m/s)
For the power estimate
For the power estimate
Atmospheric pressure for the NPSH
Vapour pressure and viscosity
📊
Calculation Results
Calculated instantly from your inputs
💧
Camp Water Supply

The well pump and the booster are sized for different flows: the well pump fills the tank over its working hours (maximum day / hours), the booster must give the peak second flow of the camp (shift change, all showers). Pump heads start from the dynamic water level (not the well depth) and from the low water level of the tank. With an elevated tank the camp may be fed by gravity; the booster then only adds the missing pressure.

Key Points:
  • ShNQ 2.04.01-22 norms and probability method (q = 5·q0·α)
  • Well pump flow and head from the dynamic water level
  • Ground or elevated tank, optional fire reserve
  • Booster flow and head, pressure switch settings, diaphragm tank
  • Pipe sizes, friction and local losses for every line
  • NPSH, setting depth and well yield checks, motor power
  • All flows in L/s and m³/h
Calculation Steps:
  1. Enter all required parameters
  2. Click "Update Calculation"
  3. Review results and analysis
Formula Variables:
Hst + s Dynamic water level (m)
α Simultaneity coefficient (-)
q0 Flow of one fixture (L/s)
LWL Low water level of the tank (m)