Cold Room & Freezer Load Calculator

✏️
Input Data
Enter your project data
Usual: chillers 80-100 mm, freezers 120-150 mm (PU).
PU / PIR 0.022, mineral wool 0.040, EPS 0.035.
Time to bring the day's intake down to the room temperature.
Used for the respiration heat of fruit and vegetables.
📊
Calculation Results
Calculated instantly from your inputs
🥶
Cold Room Load

The refrigeration unit of a cold room must remove the heat entering through the panels, the warm air coming in at every door opening, the heat of the product brought in each day (and its freezing heat in a freezer), the respiration heat of fresh fruit and vegetables and the heat of people, lights, fans and defrost. The daily total is divided by the compressor run time; the unit then has spare time for defrost and peaks.

Key Points:
  • Infiltration through the door is often the largest load in busy rooms - use strip curtains and fast doors
  • Freezing is expensive: the latent heat (about 230-300 kJ/kg) is 5-10 times the sensible cooling
  • Pull-down time: halving it doubles the product load in kW
  • Evaporating temperature ≈ room temperature − coil TD (5-7 K for fresh products, keeps the humidity high)
  • Freezer floors must be insulated and heated against frost heave
  • Typical chiller rooms: 20-60 W/m³, freezer rooms: 30-80 W/m³ of room volume
Calculation Steps:
  1. Enter all required parameters
  2. Click "Update Calculation"
  3. Review results and analysis
Formula Variables:
U Panel heat transfer coefficient (W/(m²·K))
A Wall / ceiling / floor area (m²)
m Daily product intake (kg/day)
L Latent heat of freezing (kJ/kg)
t_pull Pull-down time (h)
t_run Compressor run time (h/day)