Pipe DN Recommendation

✏️
Input Data
Enter your project data
System type automatically sets velocity limits (and, for Heating/Cooling, a verified friction-rate target). Heating/cooling are sized primarily on friction loss; fire lines by a velocity ceiling that depends on the pipe role (no minimum velocity).
Switch to "Calculate from Heat Load" to size the pipe from kW + ΔT instead of typing m³/h directly. Only available when System Type is Heating/Cooling.
Total flow rate through the pipe
Heating or cooling capacity carried by this pipe
ΔT for heating/cooling systems (typically 20°C for heating, 5-6°C for chilled water — e.g. 80/60°C heating or 6/12°C chilled water)
Used only for density in the heat-load-to-flow conversion. Heating: 70-80°C, Chilled water: 6-12°C
Pipe material affects inner diameter and roughness
📊
Calculation Results
Calculated instantly from your inputs
🔧
Smart Diameter Selection

This calculator recommends the optimal pipe diameter based on your system type and flow requirements.

Each system has specific velocity limits:

  • HVAC: 0.5-1.5 m/s (noise control)
  • Fire: by pipe role — feed main 5, cross main 8, branch line 15 m/s max; no minimum; Hazen-Williams C = 120 steel / 150 copper and plastic
  • Water: 0.6-2.0 m/s (balanced)
  • Compressed Air: 6-12 m/s (high velocity OK)

Key Points:
  • System-specific velocity limits
  • Automatic standard pipe selection
  • Alternative options provided
  • Head loss calculation included
Calculation Steps:
  1. Enter all required parameters
  2. Click "Update Calculation"
  3. Review results and analysis
Formula Variables:
D Diameter (mm)
Q Flow Rate (m³/h)
V Velocity (m/s)
Re Reynolds (-)
f Friction Factor (-)