Sanitary Fixture Calculator

✏️
Input Data
Enter your project data
Selects which method drives the Recommended Pipe boxes (main line, cold line, hot line)
TS EN 806-3: selects Table 3.x. DIN 1988-300: the smallest pipe of this material with peak-flow velocity ≤ 2 m/s is proposed
Sets the DIN 1988-300 peak-flow curve and the typical drainage K (TS EN 12056-2). TS EN 806-3 has no building types - in that mode it only affects drainage and the DIN comparison. For non-residential use, choose DIN 1988-300 as sizing method
System I: partly filled branches, 50 % filling (usual practice in Turkey / continental Europe). System II: small-bore branches, 70 % filling
Auto = from the building type (dwelling / office 0.5, school / hotel / hospital 0.7, camp 1.0). Override only for special use: public toilets / showers 1.0, laboratory 1.2
Optional, outside both standards: share of showers running at the same time (e.g. shift change in camps / dormitories). Shown as a separate check next to the standard results
Gradient of the horizontal drain (TS EN 12056-2 Annex B range 0.5–5 %)
Site check: pipe already installed on the main line before the water heater (list follows the selected material)
Site check: pipe already installed on the cold water line
Site check: pipe already installed on the hot water line
Site check: drain pipe already installed (checked at the selected slope; the minimum slope that would make it work is also shown)
📊
Calculation Results
Calculated instantly from your inputs
Sanitary
Sanitary Fixture Load Calculation

Calculate water supply and drainage loads according to TS EN 806-3 and TS EN 12056-2

Key Points:
  • TS EN 806-3 for water supply
  • TS EN 12056-2 for drainage
  • Loading units (LU) with material tables 3.1-3.8 - simultaneity built into the tables
  • Automatic pipe sizing
  • Large facility support (up to 2000 fixtures)
  • Largest single draw-off and max pipe length limits of the tables are checked
  • Above the table range = special installation (TS EN 806-3 §6)
Calculation Steps:
  1. Enter all required parameters
  2. Click "Update Calculation"
  3. Review results and analysis
Formula Variables:
LU Loading Unit (LU)
DU Discharge Unit (DU)
Qww Wastewater Flow (L/s)